Water Location Detection cable
![]() |
The WLD-Location Cable Type L detects flooding and determines the distance to the point where liquid is detected. When flooding occurs inside buildings or data centers, every second counts. Locating the flooding point makes it possible to quickly identify the exact location, even beneath floors or in inaccessible areas. The WLD-Location cable indicates the location of water, glycol, or other conductive liquid leaks. The WLD-Location Cable Type L is a sensing cable for detecting water and conductive liquids that also identifies where along the cable the leak occurred. Unlike standard WLD Type A and Type B sensing cables, which only report the presence of liquid somewhere within the entire zone, Type L also locates the position of the leak. Use it where detecting a leak is not enough and its exact location must also be identified. The maximum length of one WLD-L zone is 100 m. ![]() A 5-meter connecting cable is used to connect the location cable to monitoring units equipped with a WLD-L port (green 4-pin connector). The 10 m and 50 m cables simply snap together, with a 4-pin terminator fitted at the end. Unlike Type A and Type B sensing cables, the WLD-Location Cable Type L cannot be extended using a non-sensing extension cable. ![]() WLD Port A green 4-pin “WLD-L” port is required to connect the yellow WLD-Location Cable Type L, for example on the Perseus Industrial 310 and Perseus Industrial 315.
![]() Locating the Flooding Point Locating the liquid along the entire length of the location cable takes 15 to 30 seconds.
![]() |